Several faults of this series of soft starter for three phase induction motor, cause analysis and solutions.
Fault
Cause of fault
Solutions
Overvoltage protection
Main circuit voltage is too high
1. Check whether the main circuit voltage is too high.
2. Check whether the parameter Q24 of the overvoltage protection value is set correctly.
Undervoltage protection
Main circuit voltage is too low
1. Check whether the main circuit voltage is too low.
2. Check whether the parameter Q26 of overvoltage protection value is set correctly
Phase voltage imbalance
Three-phase power supply voltage imbalance
1. Check whether the main circuit voltage is three-phase unbalanced.
2. Check whether the parameter Q23 of the voltage imbalance protection value is set correctly.
SCR abnormality
Check whether the thyristor is short-circuited.
Leakage blocking
Check the insulation of three-phase winding to ground.
Starting timeout
Starting time is too long
1. Check whether the current limiting signal is set too small.
2. Whether the starting time limit B12 parameter is set too small.
SCR overheat
Internal radiator overheated?
Poor ventilation of the machine
1. Check whether the fan works reliably.
2. Reduce the starting frequency. Check whether the control power supply voltage is too low.
Motor temperature
motor temperature detecys by PTC thermal resistor inside the motor is too high
1. Check whether the PTC circuit is closed and the input is connected.
2. Check and correct the cause of high temperature.
Restart the motor after it has cooled down enough.
Frequent starting
Starting too often
The start frequency exceeds the set minimum start interval parameter Q09..
Frequency fault
Frequency out of range
Check and change the power supply frequency.
Zero sequence protection
Check that the three-phase leakage exceeds the design value
Tap timeout
Tapping time is too long
The starting time exceeds the set starting time limit parameter B13.
Main Technical Parameters
Item Basic parameters Load Type 3-phase high-voltage squirrel-cage asynchronous motor,
synchronous motor
AC voltage 3000---10000VAC Working frequency 50HZ / 60HZ ± 2HZ Phase sequence CMV allows to work in any phase sequence (can be set by parameter) Bypass Contactor Contactor with direct starting capacity Control power AC/DC(110-220V)±15% Specifications