Brief Introduction

Several faults of this series of soft starter for three phase induction motor, cause analysis and solutions.

Fault

Cause of fault

Solutions

Overvoltage protection

Main circuit voltage is too high

1. Check whether the main circuit voltage is too high.

2. Check whether the parameter Q24 of the overvoltage protection value is set correctly.

Undervoltage protection

Main circuit voltage is too low

1. Check whether the main circuit voltage is too low.

2. Check whether the parameter Q26 of overvoltage protection value is set correctly

Phase voltage imbalance

Three-phase power supply voltage imbalance

1. Check whether the main circuit voltage is three-phase unbalanced.

2. Check whether the parameter Q23 of the voltage imbalance protection value is set correctly.

SCR abnormality


Check whether the thyristor is short-circuited.

Leakage blocking


Check the insulation of three-phase winding to ground.

Starting timeout

Starting time is too long

1. Check whether the current limiting signal is set too small.

2. Whether the starting time limit B12 parameter is set too small.

SCR overheat

Internal radiator overheated?

Poor ventilation of the machine

1. Check whether the fan works reliably.

2. Reduce the starting frequency. Check whether the control power supply voltage is too low.

Motor temperature

motor temperature detecys by PTC thermal resistor inside the motor is too high

1. Check whether the PTC circuit is closed and the input is connected.

2. Check and correct the cause of high temperature.

Restart the motor after it has cooled down enough.

Frequent starting

Starting too often

The start frequency exceeds the set minimum start interval parameter Q09..

Frequency fault

Frequency out of range

Check and change the power supply frequency.

Zero sequence protection


Check that the three-phase leakage exceeds the design value

Tap timeout

Tapping time is too long

The starting time exceeds the set starting time limit parameter B13.

Main Technical Parameters

ItemBasic parameters
Load Type

3-phase high-voltage squirrel-cage asynchronous motor

synchronous motor

AC voltage3000---10000VAC
Working frequency50HZ / 60HZ ± 2HZ
Phase sequenceCMV allows to work in any phase sequence (can be set by parameter)
Bypass ContactorContactor with direct starting capacity
Control powerAC/DC(110-220V)±15%

Specifications

technical data of soft starter for three phase induction motor


Recommended Products

RECOMMENDED PRODUCTS
Liquid Rotor Starter

Liquid Rotor Starter

Innovative Soft Starter

Innovative Soft Starter

AC Soft Start Device

AC Soft Start Device

Soft Starter Deep Well Pump

Soft Starter Deep Well Pump

Softstarter 37KW

Softstarter 37KW

News

News

View More
Contact Us
+86 15523831294

sharon@chinasimo.com

3771550493

No.159, Economic and Technological Development Zone, Xi'an, Shaanxi Province, China

Meeting your motor model needs is our eternal pursuit

tina.gatn@wolongcne.com

TEL

+86 15523831294

Motor Price Inquiry

WhatsApp