Brief Introduction
The solid state soft starter uses yellow LEDs to indicate that a fault has occurred and shows the corresponding fault information on the LCD display. There are 19 kinds of protection functions. When the protection function of series solid state soft starter is activated, it stops immediately and the LCD display shows the current fault. Users can analyze the fault according to the fault content.
Fault
Cause of fault
Solutions
Main power supply phase loss
Lack of phase sequence at startup or during operation
Check whether the three-phase power supply is reliable phase?
Phase sequence error
Phase sequence reversed
1. Adjust the phase sequence of the three-phase main power supply.
2. Set B09 parameter to not detect phase sequence.
Parameter loss
Setting parameters missing?
Check each function item setting and reset
Overload protection
After a certain time, the current is still too high, resulting in motor overload.
1. Check and correct the cause of overload and check if the current limit multiplier is set too low.
Check whether the starting time is set too long.
3,Check whether the motor overload protection level is set reasonably.
4. Check whether the motor rated current is set correctly.
Running overcurrent
Load suddenly increased?
Load fluctuates too much?
1. Adjust the load running condition
2. Check whether the B03 parameter item is set too small.
Underload protection
Motor running current lower than rated current
1. Check the cause of underload and make corrections
2. Check whether the setting is according to the operating conditions.
Phase current imbalance
Three-phase current imbalance
1. Check if the three-phase current imbalance exceeds the imbalance protection level set in parameter item B01.
2. Adjust the load operating conditions.
Main Technical Parameters
Item Basic parameters Load Type 3-phase high-voltage squirrel-cage asynchronous motor,
synchronous motor
AC voltage 3000---10000VAC Working frequency 50HZ / 60HZ ± 2HZ Phase sequence CMV allows to work in any phase sequence (can be set by parameter) Bypass Contactor Contactor with direct starting capacity Control power AC/DC(110-220V)±15% Transient overvoltage protection dv/dt absorption network Start frequency 1-3 times/hour Environmental conditions Ambient temperature: -20-+50℃;
Relative humidity: 5%--95% non-condensing;
Altitude less than 1500 meters (more than 1500 meters need to be de-rated)Specifications